1. Overview of the 1500A High Current Generator:
The 1500A high current generator is specially designed and manufactured for electrical equipment tests in power departments and industrial and mining enterprises, such as current load tests and temperature rise tests for various switches, current transformers, and other electrical equipment.
The 1500A high current generator adopts an integrated design, featuring stepless adjustment of output current, balanced current rise, wide load variation range, convenient operation, safety, and reliability. It is an ideal equipment for current rise or temperature rise tests in industrial and mining enterprises.
2. Parameters of the 1500A High Current Generator:
1, Capacity: 7KVA
2, Input voltage: AC220V±10% 50Hz
3, Input current: 35A
4, Output current: 0-1500A
5, Output voltage: 5V
6, Current transformer ratio: 1500:5
7, Display mode: Digital display
8, Display accuracy: 0.5 class
9, Weight: 40
10, Structure: Integrated
3. Operating Environment:
1, Working power supply: 220V ±10% 50HZ
2, Ambient temperature: -10℃—40℃
3, The product should be placed in an environment free from gases, vapors, chemical dust, dirt, or other explosive media that seriously affect transformer insulation.
4. Usage Methods and Precautions:
1, The instrument must be properly grounded.
2, Connect the power supply, turn on the switch, the red indicator light will be on, and the current generator is ready for current rise.
3, Rotate the voltage regulator evenly clockwise, and observe the output current indicator on the operation panel until the desired high current is reached.
4, During the test, if any abnormal phenomenon is found, cut off the power immediately, find out the cause, and then proceed with the test.
5, After the test, the voltage regulator must be returned to zero, cut off the power with the air switch, disconnect the working power, and remove the test wiring in reverse order to ensure safety.
5. Precautions:
1, For newly installed or long-term unused equipment, before operation, measure the insulation resistance between coils and between coils and ground with a 1500 megohmmeter. It can be used only when the resistance value is not less than 0.5 megohm.
2, During use, the main unit and operation panel of the high current generator must be reliably grounded to ensure safety.
3, During use, the current should be increased slowly and evenly, and avoid excessive vibration during handling.
4, The contact surface between the voltage regulator and the carbon brush should be kept clean. If necessary, wipe it clean with cotton yarn dipped in 90% alcohol.
5, This equipment should be stored indoors in a clean, ventilated, and dry place.
6. Completeness of the 1500A High Current Generator Set:
1, Main unit of high current generator One set
2, Product certificate One copy
3, Product instruction manual One copy