High Current Generator
It is specially designed and manufactured for electrical equipment tests in power departments and industrial and mining enterprises, such as current load tests and temperature rise tests for various switches, current transformers, and other electrical equipment.
This product features small size, light weight, integrated structure, stepless adjustment of output current, balanced current rise, wide load variation range, 0.5-class current transformer, digital display, beautiful appearance, reliable operation, simple operation, and safety. It is an ideal equipment for current rise tests in industrial and mining enterprises.
Product Parameters:
◆ Rated capacity of current generator: 5KVA
◆ Rated capacity of voltage regulator: 5KVA
◆ Rated input voltage: 220V
◆ Rated input current: 22.7A
◆ Rated output current: 0-1000A
◆ Rated output voltage: 5V
◆ Structure type: Integrated
◆ Power supply phase: Single phase
◆ Test accuracy: 1%
Operating Conditions:
◆ Working power supply: 220V ±10% 50Hz
◆ Ambient temperature: -10℃~+50℃
◆ The product should be placed in an environment free from gases, vapors, chemical dust, dirt, or other explosive media that could seriously affect transformer insulation.
Working Principle:
◆ The instrument must be properly grounded.
◆ After connecting the working power supply, turn on the switch, the red indicator light will illuminate. Press the start button, the green indicator light will illuminate. Connect the output terminal to the test object, and the current generator is ready for current rise.
◆ Rotate the voltage regulator evenly clockwise, and pay attention to the output current indicator on the operation panel until the required high current is reached.
◆ During the test, if any abnormal phenomenon is found, immediately cut off the power supply, identify the cause, and then proceed with the test.
◆ After the test, the voltage regulator must be returned to zero, press the stop button to cut off the power supply, and then disconnect the test wiring to ensure safety.
Precautions:
◆ For newly installed transformers or those not used for a long time, measure the insulation resistance between coils and between coils and ground with a 1500 megohmmeter before operation. Only when the resistance value is not lower than 0.5 megohm can it be used.
◆ During use, the current generator transformer and the operation console must be reliably grounded to ensure safety.
◆ When in use, the current should be increased slowly and evenly, and avoid excessive vibration during handling.
◆ The contact surface between the voltage regulator and the brush should be kept clean. If necessary, wipe it clean with cotton yarn dipped in 90% alcohol.
◆ This equipment should be stored indoors in a clean, ventilated, and dry place.