Resonant Step-Up Device
Product Features:
The resonant step-up device is suitable for boosting voltage in the calibration of various types of CVTs at voltage levels of 35kV, 66kV, 110kV, 220kV, 330kV, and 500kV. This TLHG-605 CVT resonant step-up device utilizes the principle of series resonance, adopts stepless manual inductance adjustment technology and the method of connecting reactors in series, which significantly reduces the required power supply, test equipment volume, and weight. It also simplifies wiring and operation, making it convenient for field testing. It is the preferred device for power metering and high-voltage testing professionals.
The TLHG-605 CVT resonant step-up device produces good output voltage and current waveforms;
The TLHG-605 CVT resonant step-up device requires low capacitance. The required power supply capacity is 1/Q times the test capacity, and the Q value can reach 20-60;
This device does not require overvoltage protection. When the test object breaks down, the system detunes, the resonant high voltage disappears, and the reactor immediately limits the short-circuit current, preventing further damage to the test object.
Product Parameters:
110/1 220/0.5 220/1 330/0.5 330/1 500/0.5 500/1
Voltage Regulating Control Box
Capacity 5kVA 5kVA 5kVA 5kVA 6kVA 10kVA 10kVA 15kVA 10kVA 15kVA
Rated High Voltage (KV) 24.2 45.7 76.2 76.2 152.4 152.4 209.6 228.6 303.1 346.4
High Voltage Current 0.5A 0.5A 0.5A 1A 0.5A 1A 0.5A 1A 0.5A 1A
Reactor
Quantity 1 1 2 2 4 4 6 4 8 6
Single Reactor
Withstand Voltage 40kV 50kV 40kV 40kV 40kV 40kV 60kV 40kV 40kV 60kV
Single Reactor
Capacity 20kVA 25kVA 20kVA 40kVA 20kVA 40kVA 20kVA 60kVA 20kVA 60kVA