| Cable Fault Location System Darui Electric recommends for you Pinpointing: |
Path:
Simple and convenient operation, no professional training required
Output voltage peak up to 1000V (open circuit voltage)
Detection distance <20Km
Detection depth ≤ 3m
Route error <5cm
Induced fault point distance ≤ 30m
Distance Measurement:
Rugged integrated handcart structure with powerful impact energy.
Internally integrated DC high-voltage generator, high-voltage impulse capacitor, automatic ignition/discharge sphere gap unit, current coupling unit, centralized automatic control unit, easy-to-operate cable fault impulse generator.
Wide wheels (diameter 25CM), lightweight and compact design, ensuring smooth long-distance movement on various road conditions.
Quickly locate and pinpoint low-resistance, open-circuit, high-resistance leakage, and flashover faults of power cables of various voltage levels.
Built-in high-voltage output terminal, output is high-voltage silicone coaxial cable, simple wiring, safe and reliable.
Test modes: Arc reflection method / Multiple pulse method,
DC arc reflection method / DC multiple pulse method
Current sampling method (built-in)
DC current sampling method (built-in)
DC output (built-in)
Sampling signal types: Arc reflection / Multiple pulse, current sampling, low-voltage pulse.
Built-in DC high-voltage output: 0~32KV negative polarity Output current: 50mA
Built-in pulse impulse capacitor: 0~35KV 4μF Capacitor energy 2450J joules
Built-in sphere gap impulse discharge: Weak current controlled solenoid valve air gap, impulse discharge cycle 3—12 seconds adjustable, and specially designed silencing device to meet the requirement of silence for starting cable faults.
Sampling frequency: 30MHz, 60MHz, 120MHz, 200MHz multiple sampling frequencies, higher test accuracy.
Test distance: Up to 165Km.
Test pulse: 0.2~9.9μs, arbitrarily adjustable.
Pulse method error:
Rough measurement relative error: not greater than ±0.25%;
Rough measurement error: for cables less than 2 kilometers, not exceeding 1 meter;
for cables more than 5 kilometers, not exceeding 2 meters.
Protection:
Zero voltage position protection: prevents misoperation, ensures safety of personnel and tested equipment;
After pressing the "Disconnect" key, residual charge is quickly and automatically discharged through built-in safety devices to ensure safety.
Dimensions: 400*300*800mm