Transformer Loss Parameter Tester

Recommended by Darui Electric
 

Main Indicators of Transformer Loss Parameter (500V) Tester

1. Input Characteristics

Voltage measurement range: 0~750V wide range.

Current measurement range: 0~80A, all internal automatic range switching.

2. Accuracy

Voltage, current, ±0.2%

Power: ±0.5% (CosΦ>0.1), ±1.0% (0.02<CosΦ<0.1)

3. Operating temperature: -10℃~+40℃

4. Insulation: (1) Insulation resistance between voltage/current input terminals and the case ≥100M?.

             (2) The working power input terminal withstands a power frequency of 2kV (effective value) for 1 minute test against the case.

5. Dimensions: 38cm×28cm×15cm

6. Weight: 3kg

 

Technical Parameters of Transformer Loss Parameter (500V) Tester

■ Voltage (V): Range 500V ± (0.25% of reading + 0.25% of range)

■ Current (A): Range 80A ± (0.25% of reading + 0.25% of range)

■ Power (W): ± (0.25% of reading + 0.25% of range)

■ Power factor: Range 0~1, accuracy ±5 digits

■ Frequency: 40~60Hz, 0.05%

■ Measurement accuracy: 0.5 class

■ Power supply: AC 220V±10%, 50Hz±2%

■ Total power consumption: less than 25W

 

Precautions

1. Do not touch the metal parts of the test leads during measurement to avoid electric shock.

2. The measurement wiring must be strictly followed according to the manual, otherwise the consequences will be borne by the user.

3. Before testing, carefully check whether the set parameters are correct.

4. Use a power outlet with a ground wire.

5. Do not work under overvoltage or overcurrent conditions.

6. During short-circuit test, the short-circuit on the non-energized side must be good, otherwise it will affect the test results.

7. When performing short-circuit test, if the high-voltage or medium-voltage side bushing is equipped with a ring-type current transformer, the secondary of the current transformer must be short-circuited before the test.

8. The test wiring must be carried out with the tested line grounded to prevent electric shock from induced voltage. All short-circuit, grounding, and lead wires should have sufficient cross-section and must be connected securely. The test organization should be rigorous, and communication should be smooth to ensure the safe and smooth progress of the test work.

Features

1. Uses a 240×128 dot matrix LCD to display three-phase voltage, current, low-voltage side voltage, power, power factor and other parameters simultaneously.

2. Can measure no-load current, no-load loss, short-circuit voltage, and short-circuit loss of various types of transformers.

3. Wide linear range, good reading repeatability, and stable performance.

4. Ensures accurate measurement of power factor from 0.000 to 1.000, especially suitable for detection of low power factor loads.

5. Convenient latching ensures simultaneity of measurement data and ease of operation.

Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.

 


 

WeChat QR Code
💬
💬 Message ✕

Hello! Have you found what you need? Contact us directly online!

Leave a Message for Consultation
Yangzhou Darui Electric Co., Ltd.
主营产品:Dielectric Loss Tester、Transformer Ratio测试仪、Loop Resistance Tester、高压None线核相仪、Insulation Resistance Tester、Partial Discharge Tester、Cable Fault Tester、DC Resistance Tester等。
☎ Phone: 18952707000(关经理)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com
Verification Code
By submitting, you agree to ourTerms of ServiceandPrivacy Policy
🏠 网站Home📞 一键拨号✉ Contact Us