| 22KV/44KVA Variable Frequency Series Resonance Dary Electric recommends for you Main technical parameters and functions of the device 1. Rated capacity: 44kVA; 2. Input power: single-phase 220V or three-phase 380V voltage, frequency 50Hz; 3. Rated voltage: 22kV 4. Rated current: 2A 5. Working frequency: 20-300Hz; 6. Output waveform: sine wave 7. Waveform distortion rate: output voltage waveform distortion rate ≤1%; 8. Working time: continuous 5min allowed under rated load; overvoltage 1.1 times for 1 minute; 9. Temperature rise: after continuous operation for 5min under rated load, temperature rise ≤65K; 10. Quality factor: device's own Q≥30 (f=45Hz); 11. Protection functions: overcurrent, overvoltage, and flashover protection for the test object (see variable frequency power supply section for details); 12. Measurement accuracy: system effective value class 1.5; Test object and test requirements AC withstand voltage test for 10kV/300mm2 cable length 1km, capacitance ≤0.3755uF, test frequency 30-300Hz, test voltage 22kV, test time 5min. Working environment 1. Ambient temperature: -100℃~50℃; 2. Relative humidity: ≤90%RH; 3. Altitude: ≤1000 meters; The device capacity is set to 44kVA/22kV, divided into two reactor sections, each reactor is 22kVA/22kV/1A/92H. The series and parallel connection of reactors can meet the test requirements of the above test object. GB10229-88 "Reactors" GB1094 "Power Transformers" GB50150-2006 "Standard for Handover Test of Electrical Equipment Installation Engineering" DL/T 596-1996 "Preventive Test Regulations for Power Equipment" GB1094.1-GB1094.6-96 "Degrees of Protection Provided by Enclosures" GB2900 "Electrotechnical Terminology" GB/T16927.1~2-1997 "High-Voltage Test Techniques" |