Partial Discharge Detector
Darui Electric recommends
Main Technical Specifications
1. Capacitance range of test object: 6pF~250μF.
2. Detection sensitivity and allowable current
|
Input Unit Number |
Tuning Capacitance Range |
Sensitivity (pC) (Unbalanced Circuit) |
Allowable RMS Current |
|
|
Unbalanced Circuit |
Balanced Circuit |
|||
|
1 |
0 ~ 25 ~ 100pF |
0.02 |
30mA |
0.25A |
|
2 |
25 ~ 100 ~ 400pF |
0.04 |
50mA |
0.5A |
|
3 |
100 ~ 400 ~ 1500pF |
0.06 |
120mA |
1A |
|
4 |
400 ~ 1500 ~ 6000pF |
0.1 |
0.25A |
2A |
|
5 |
1500 ~ 6000 ~ 25000pF |
0.2 |
0.5A |
4A |
|
6 |
0.006 ~ 0.025 ~ 0.1μF |
0.3 |
1A |
8A |
|
7 |
0.025 ~ 0.1 ~ 0.4μF |
0.5 |
2A |
15A |
|
8 |
0.1 ~ 0.4 ~ 1.5μF |
1 |
4A |
30A |
|
9 |
0.4 ~ 1.5 ~ 6.0μF |
1.5 |
8A |
60A |
|
10 |
1.5 ~ 6.0 ~ 25μF |
2.5 |
15A |
120A |
|
11 |
6.0 ~ 25 ~ 60μF |
5 |
25A |
200A |
|
12 |
25 ~ 60 ~ 250μF |
10 |
50A |
300A |
|
7R |
Resistance |
0.5 |
2A |
15A |
Table 1: Detection sensitivity and allowable current values for input units
3. Elliptical scanning time base
(1) Frequency: 50Hz;
(2) Rotation: in steps of 30°, rotatable up to 120°;
(3) Display mode: ellipse - straight line.
4. Display unit
Uses a 98×84 (mm) rectangular oscilloscope tube with brightness and focus adjustment knobs.
5. Amplifier
(1) 3dB low-frequency cutoff: selectable 10, 20, 40kHz;
(2) 3dB high-frequency cutoff: selectable 80, 200, 300kHz;
(3) Gain adjustment: coarse adjustment in 6 steps, with 20±1dB difference between steps, fine adjustment range > 20dB;
(4) Asymmetry of positive and negative pulse response < 1dB.
6. Time window
(1) Window width: adjustable, 15°~150° at 50Hz;
(2) Window position: each window can be rotated 0°~170°;
(3) Two time windows can be opened separately or simultaneously.
7. Pulse peak meter
(1) Linear scale pointer meter: 0—100, error ±5% (based on full scale).
(2) Logarithmic scale pointer meter: 0—10—100, error ±5% (based on full scale).
(3) Digital meter: 3.5-digit LED display, 0—100, error: ±3% (based on full scale).
8. Test voltage meter
(1) Uses a 3.5-digit digital meter, can read test voltage or pC value;
(2) This system uses a capacitive voltage divider, 0~100kV direct reading;
(3) Error: ±3%.
9. Zero marking system
The internal peak marker generator produces peak markers (the PD detector must be connected to a 1000:1 capacitive voltage divider to generate them).
10. Calibration pulse generator (built-in)
(1) Calibration square wave voltage amplitude: 10mV~4V in 11 steps;
(2) Calibration square wave pulse rise time: ≤60nS;
(3) Calibration square wave pulse fall time: ≥100uS;
(4) Discharge calibration range (when high-voltage injection capacitance is 100pF): 1, 2, 4, 5, 10, 20, 40, 50, 100, 200, and 400pC;
(5) Repetition frequency: same as time base frequency, 50Hz;
(6) Pulse rotation: 0~360°, divided into two ranges.
This product is designed and developed by our factory based on the characteristics of the cable industry, specifically for partial discharge testing of cross-linked cables. It has a built-in calibration pulse generator, higher integration, small size, and simple operation.
Note: The above information and technical parameters are compiled and published by Yangzhou Darui Electric Co., Ltd.