Product Description

10A Transformer Color Screen Capacity Tester



Darui Electric recommends



Test Purpose

Measurement of transformer capacity, no-load current, no-load loss, short-circuit voltage, and short-circuit (load) loss

Working Power Supply Input Voltage 185Vac~250Vac

Allowable Input Voltage      85Vac~264Vac

Frequency              50/60Hz

Input Power          40VA

AC Voltage Range      10~650V

Resolution            0.001V

Accuracy            0.2%±0.001V

AC Current Range      0.5~60A

Resolution            0.001A

Accuracy            0.2%±0.001A

Resolution            0.001Hz

Accuracy            0.2%±0.001Hz

Power Range          0~39kW

Resolution            0.001kW

Accuracy            <±0.5%(CosΦ>0.1),±1.0%(0.02<CosΦ<0.1)



Function Description

①LCD Display: Used for Chinese character display, guiding operation, and intuitive reading.

②Fuse Box: Protects the instrument for normal operation.

③Ground Terminal: Connected to the earth to ensure personal safety.

④Panel Printer: Prints measurement results.

⑤Terminals for measuring transformer capacity and active load.

⑥Terminals for measuring transformer no-load and load loss.

⑦External 220VAC power socket, used when charging or using external power supply.

LCD Panel

The LCD display interface mainly has eleven screens, including the main menu and ten function interfaces, which are described in detail below.

Main Menu Interface

The main menu has ten options: Capacity Test, Parameter Settings, Active Load, Single-Phase No-Load, Three-Phase No-Load, Single-Phase Short-Circuit, Three-Phase Short-Circuit, Result Query, Electrical Parameters, and Harmonic Analysis. When the cursor points to a function option, that option is displayed in reverse color. As shown in Figure 4, the selected item is 'Capacity Test'. Use the up, down, left, and right keys to change the cursor position. At this point, press the OK key to enter the selected function display screen. The bottom line is the prompt line, displaying the current date and time, the internal battery voltage amplitude, and the remaining battery percentage, so that the battery status of the instrument can be known in time, and whether the instrument needs charging to avoid failure to work normally on site due to lack of timely charging.



The 10A transformer color screen capacity tester manufacturer's main menu has ten options: Capacity Test, Parameter Settings, Active Load, Single-Phase No-Load, Three-Phase No-Load, Single-Phase Short-Circuit, Three-Phase Short-Circuit, Result Query, Electrical Parameters, and Harmonic Analysis





Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.

 


WeChat QR Code
💬
💬 Message ✕

Hello! Have you found what you need? Contact us directly online!

Leave a Message for Consultation
Yangzhou Darui Electric Co., Ltd.
主营产品:Dielectric Loss Tester、Transformer Ratio测试仪、Loop Resistance Tester、高压None线核相仪、Insulation Resistance Tester、Partial Discharge Tester、Cable Fault Tester、DC Resistance Tester等。
☎ Phone: 18952707000(关经理)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com
Verification Code
By submitting, you agree to ourTerms of ServiceandPrivacy Policy
🏠 网站Home📞 一键拨号✉ Contact Us