YD-6628 Automatic Transformer Turns Ratio Tester
Darui Electric recommends
Main Features
The instrument adopts two output test power modes: single-phase and three-phase;
It can measure the turns ratio and connection group (or polarity) of transformers with connection groups such as single-phase, Y/y, Y/d, D/y, D/d, etc.
It can measure the turns ratio and angle of Z-type transformers at any angle (without inputting angle values);
It has the function of testing transformer tap changers;
The unique angle testing function is important for the winding connection of transformer manufacturers;
The instrument can store test data of 10 transformers internally, with each group of data having up to 40 tap positions;
The instrument uses a large-screen LCD, with full Chinese menu prompts for easy operation, and a micro printer can print out all test data;
It has USB storage and non-volatile clock functions;
It features fast measurement speed, high accuracy, shock resistance, and portability.
Product Parameters
1. Technical Indicators
Turns ratio measurement range: 0.9—5000
Turns ratio measurement accuracy: 0.1 class (0.9—1000)
0.2 class (1000-5000)
Connection group measurement: 1-12
Angle measurement: ±0.2%+0.2 degrees
Test voltage: single-phase AC200V, 100V automatic switching;
Three-phase line voltage AC60V 50HZ
Dimensions: 403mm×330m×178mm
Weight: 7Kg
2. Operating Conditions
Ambient temperature: -10 to 50℃
Ambient humidity: ≤85%RH
Power supply: AC220V ± 10%
Power frequency: (50 ± 1) HZ
Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.
![]()