YTC3317 Automatic Transformer Turns Ratio and Vector Group Tester
Darui Electric recommends for you
Product Introduction
Traditional transformer turns ratio testers use a ratio bridge to measure the turns ratio of transformers, which is cumbersome and has a narrow measurement range, no longer meeting the fast-paced and high-efficiency requirements of modern testing. Our developed tester is compact, lightweight, highly accurate, and stable.
Product Aliases:
Transformer Turns Ratio and Vector Group Tester, Turns Ratio and Vector Group Tester, Automatic Transformer Turns Ratio Tester, Automatic Turns Ratio and Vector Group Tester, Transformer Turns Ratio and Vector Group Measuring Instrument, Transformer Turns Ratio Measuring Instrument, Automatic Transformer Turns Ratio Measuring Instrument.
Product Features:
1.Automatically measures the connection group;
2. Automatically performs group transformation;
3、Automatically switches phase sequence;
4、Automatically switches range;
5、Automatically calibrates the meter;
6、After inputting the standard turns ratio, it can automatically calculate the relative error;
7、Once the measurement is completed, the test voltage is automatically cut off;
8、Settings and measurement results are automatically saved, and previous data can be viewed;
9、For measuring on-load tap-changing transformers, only one turns ratio input is required.
Product Parameters:
1.Turns ratio measurement range: 1—10000
2. Vector group: 1—12 o'clock
3、Accuracy: 1-1000 0.2 class
1000-10000 0.5 class
4、Power supply: AC220V ±10%, 50HZ
5、Operating ambient temperature: -5℃ ─ 40℃
6、Operating ambient humidity: <85%
7、Dimensions: 430×320×215mm3
8、Weight: 8kg
Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.